HVDC Disconnectors
Disconnectors (DSC) for HVDC applications are designed to specific constraints and requirements typical for DC applications, which are quite different compared to AC applications. They are requested to withstand DC voltage open gap and to ground to ensure safety for the people in the substation and to permit proper and safe layout configuration. In some cases, like for filter applications, they are requested to break a sum of harmonic currents at a certain voltage (amply smaller than the rated voltage of the disconnector) due to the ripple created by harmonics on the reactances.
All these DC disconnectors take advantage of huge experience and installed base of AC disconnector technology delivered worldwide in regards to design technology and quality, e.g. supplier qualification, assembly processes or ISO conformity.
- Self-protected design of contacts (L-type contact), preventing pollution deposit and hot spots
- HVDC design of post insulators
- High value of minimum creepage distance enforcing height
- Dedicated shed profiles
- Specific layout design (also 2 or 3 post insulators for each contact side)
- High seismic performances
- Special design of anti-corona rings
EN15-702